TECHNICAL MANUAL 2013
SPLIT MONO DC INVERTER
MODELS
BDS28A
BDS35A
This manual has been created for informative purpose. The company declines every responsibility for the results of projecting or installation based on the explanations and the technical specifications given
in this manual. Is besides forbidden the reproduction under any form of the texts and of the figures contained in this manual.
Zobrazit stránku 0
1 2 3 4 5 6 ... 35 36

Shrnutí obsahu

Strany 1 - SPLIT MONO DC INVERTER

TECHNICAL MANUAL 2013 SPLIT MONO DC INVERTER MODELS BDS28A BDS35A This manual has been created for in

Strany 2 - MTE01028D2505-00

10 6. PRINTED CIRCUIT BOARD 6.1 Indoor unit: BDS28A, BDS35A No Part name 1 DC fan 2 Microswitch 3 Electrostatic precipitation 4 Small up & down

Strany 3

11 7. Control functions 7.1. Temperature Parameters • Indoor preset temperature (Tpreset) • Indoor ambient temperature (Tamb) 7.2. Basic functions

Strany 4 - 1. SPECIFICATIONS

12 7.2.2 Dehumidifying mode 7.2.2.1 The condition and process of dehumidifying If Tamb. > Tpreset, DRY mode will act, the indoor fan, outdoor fan

Strany 5 - 1010(*2/1

13 7.2.3.3 Protection function ♦ Anti-cold – wind protection In HEAT mode, in order to prevent the indoor unit from blowing out cold wind, each time

Strany 6 - 2. CHARACTERISTICS DATA

14 ② Protection a) In cooling operation, protection is the same as that under the cooling mode; b) In heating operation, protection is the same as th

Strany 7 - 541162 163

15 ⑦ Faults of temperature sensors Designation of sensors Faults Indoor ambient temperature The sensor is detected to be open-circuited or short-c

Strany 8 - TINUROODTUOTINUROODNI

16 8.3 Flashing LED of Indoor/Outdoor unit and primary judgement Display Method of Indoor Unit Indicator Display (during blinking, ON 0.5s and OFF 0.

Strany 9 - PRINTED CIRCUIT BOARD

17 10 Malfunction protection of jumper cap C5 Blinks 15 times Wireless remote receiver and button are effective, but can not dispose the related

Strany 10 - 6. PRINTED CIRCUIT BOARD

18 19 Decrease frequency due to high air discharge F9 Blinks 9 times Blinks twice All loads operate normally, while operation frequency for comp

Strany 11 - 7. Control functions

19 30 Module high temperature protection P8 Blinks 19 times During cooling operation, compressor will stop while indoor fan will operate; Durin

Strany 12 - 6min 3min 6min

2 Serie / Series / Serie / Serie TECHNICAL MANUAL MONO DC INVERTER Emissione / Issu

Strany 13

20 42 Indoor unit and outdoor unit does not match LP Blinks 19 times Blinks 16 times compressor and outdoor fan motor can’t work Indoor unit and

Strany 14

21 8.4. How to check simply the main part 8.4.1 Indoor Unit: 8.4.1.1 Temperature sensor malfunction (F1/F2) F1 and F2 malfuncti

Strany 15 - 8. TROUBLESHOOTING

22 8.4.1.2 Indoor fan does not operate (H6 Malfunction) Possible causes: 1. Fan motor is locked; 2. The feedback terminal of PG motor is not connecte

Strany 16

23 8.4.1.3. Jumper cap malfunction (C5) Possible causes: 1. There is no jumper cap on the controller; 2. Jumper cap is not inserted properly and tigh

Strany 17

24 8.4.1.4 Communication Malfunction (E6) 1. Check if connection wire between indoor and outdoor units and wire inside the unit are connected well. 2

Strany 18

25 8.4.2 Outdoor Unit: 8.4.2.1 Key detection points Test2Test4Test1Test3Test5Test6Test7Test8 Test9 Test point SN Test point Related specification

Strany 19

26 8.4.2.2. Capacitor charging malfunction (Fault with outdoor unit) (AP1 below refers to the outdoor control panel) Main detection point: • Use AC

Strany 20

27 • If the working loads of the machine are too hight? If the radiation is good? • If the charge volume of refrigerant is correct? Fault diagnosis

Strany 21

28 8.4.2.4. High temperature and overload protection diagnosis (AP1 herinafter refers to control board of the outdoor unit) Main detection point: ● I

Strany 22

29 8.4.2.6 Diagnosis for compressor Out of step (synchronism)(AP1 hereinafter refers to control board of the outdoor unit) Main detection point: ● Wh

Strany 23

3 Index 1. SPECIFICATIONS ...

Strany 24

30 8.4.2.8 Power factor correction (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the outdoor unit) Main detec

Strany 25 - 8.4.2 Outdoor Unit:

31 8.4.2.9 Communication malfunction (following AP1 for outdoor unit control board) Main detection point: ● Detect the indoor and outdoor units conne

Strany 26

32 Appendix 1: Resistance table for indoor/outdoor ambient temperature sensors (numerical value of resistance) (15K) Temp. (°C) Resistance (kΩ) Tem

Strany 27 - Fault diagnosis process:

33 Appendix 2: Resistance table for indoor/outdoor tube temperature sensor (20K) Temp. (°C) Resistance (kΩ) Temp. (°C) Resistance (kΩ) Temp. (°C)

Strany 28

34 Appendix 3: form for indoor/outdoor unit’s air exhaust temperature sensor numerical value of resistance Temp. (°C) Resistance (kΩ) Temp. (°C) R

Strany 30

Via Gettuglio Mansoldo (Loc. La Macia) 37040 Arcole Verona, Italy Tel. +39 - 045.76.36.585 r.a. Fax +39 - 045.7

Strany 31

4 1. SPECIFICATIONS Models of indoor units BDS28A BDS35A Rated voltage 220-240V ~50Hz kW 2,5(0,7 ~ 4,4) 3,5(0,7 ~ 4,5) Total capacity Btu/h 8,5

Strany 32

5 Fan motor capacitor μF / / Air flow volume of outdoor unit m³/h 2000 2000 Fan type-piece Axial-flow Fan diameter mm Φ445 Φ445 Defrosting m

Strany 33

6 2. CHARACTERISTICS DATA 2.1 Operation characteristic curve Cooling0246810505151 0 20 30 40 60 70 80 90020304060708090Compressor speed (rps)Current

Strany 34

7 Heating: Temperature conditions (°C) Standard pressure Heat exchanger pipe temp. Indoor Outdoor Model name P(MPa) T1 (°C) T2 (°C) Indoor fan spee

Strany 35

8 4. REFRIGERANT DIAGRAM TINUROODTUOTINUROODNIHEATEXCHANGE(EVAPORATOR)HE ATEXCHANGE(CONDENSER)COMPRESSORGAS SIDE3-WAY VALVELIQUID SIDE2-WAY VALVECOOL

Strany 36

9 5. ELECTRICAL CIRCUIT DIAGRAM 5.1 Indoor units: BDS28A, BDS35A RT2RT10L-OUTAC-LYEGNBNBKBUGENERATORCOOL PLASMACONN WIREYEGN0PEM2M4M3RECEIVERANDEVAPO